Electrical Network Calculations
Understand the electrical network calculations used by Unwaste EMS.
Electrical Network Calculations
Assumptions
Electrical network calculations are performed per connection. Connections are separate from each other (there should be no energy flows between connections) and are often geographically separated, so they are a sensible boundary for both calculations and database partitioning.
For a given connection, the electrical installation is modeled as a tree of circuits.
Circuits can be metered or unmetered:
A metered circuit has its own energy meter and can calculate both total consumption and residual consumption.
An unmetered circuit has no meter. It cannot measure bidirectional energy flow, so its
energyImported/energyReturnedmust be handled by assumptions described below.
In the current model, the system does not track phases (L1/L2/L3) for calculations. If values are collected per phase, they are summed into a single value.
Elements in the circuit tree
Circuit
A circuit is the structural element of the tree. A circuit can have child circuits and can also have leaf elements connected directly under it (production, storage, devices).
Metered circuit readings
A metered circuit provides two energy readings (as shown in the diagram):
energyImported[Wh] — energy entering this circuit from its parent circuitenergyReturned[Wh] — energy flowing from this circuit back to its parent circuit
These two values are read directly from this circuit's own meter.
Unmetered circuit assumptions
An unmetered circuit has no meter, so the system cannot measure how much energy flowed in both directions.
For unmetered circuits the model assumes:
energyReturned = 0energyImported = energyUsedChildren
This means: an unmetered circuit is treated as if all energy needed by its children is "imported" from the parent, and none is "returned" upward (because it cannot be measured).
energyUsedChildren for a circuit is defined in the calculation section below.
Production
Production is an element connected under a circuit (a leaf element). It represents any source that injects energy into the installation, for example solar PV inverters or wind turbines.
Production provides:
energyProduced[Wh] — total energy generated
(Use energyProduced consistently; avoid energyProduction.)
Storage
Storage is an element connected under a circuit (a leaf element). It represents a device that can both absorb and return electrical energy (currently: a battery).
Storage provides:
energyStored[Wh] — energy charged into storageenergyRetrieved[Wh] — energy discharged from storagechargeLevel[%] — state of chargefreeStorage[Wh] — remaining "free space", calculated fromchargeLeveland configured storage capacity
Devices
Devices are elements connected under a circuit (leaf elements). They represent controllable loads (execution units).
A device may provide:
energyConsumption[Wh] — device energy use
Calculations for a single circuit
This section explains how calculations are performed for one circuit, and how child circuits affect the result.
A key rule used throughout:
When a circuit needs a "sum below it", it sums only its direct children (child circuits and directly connected leaf elements).\nValues for deeper levels are already included inside each child circuit's totals.
Step 1: Calculate energyUsedChildren for a circuit
For each circuit, define:
energyUsedChildren = (sum of energyUsedChildren of all child circuits) + (sum of energyConsumption of devices connected directly to this circuit)
Notes:
Child circuits contribute via their
energyUsedTotal(their own subtree totals).Devices connected directly to this circuit contribute via their
energyConsumption.Production and storage are not part of
energyUsedChildrendirectly, because they affect the energy balance viaenergyProduced,energyStored, andenergyRetrievedin Step 2.
This definition is also what an unmetered circuit uses as its assumed import:
energyImported = energyUsedChildrenenergyReturned = 0
Step 2: Calculate subtree totals for production and storage
For a circuit, define these subtree totals as sums of direct children:
energyProduced= sum ofenergyProducedfrom:production elements connected directly to this circuit, and
child circuits' own
energyProducedtotals (already including their deeper levels)
energyStored= sum ofenergyStoredfrom:storage elements connected directly to this circuit, and
child circuits'
energyStoredtotals
energyRetrieved= sum ofenergyRetrievedfrom:storage elements connected directly to this circuit, and
child circuits'
energyRetrievedtotals
This matches the idea in the diagram: production and retrieved energy "flow into" the circuit balance, while stored and returned energy "flow out".
Important clarification:
energyImportedandenergyReturnedare never summed from child circuits. They are meter readings (or assumptions) for the circuit being calculated.
Step 3: Total energy consumption for a circuit (energyUsedTotal)

Based on the law of conservation of energy, the total energy flowing into a circuit (from import, local production, and storage discharge) must equal the total energy flowing out of that circuit (to export/return, storage charging) plus the energy consumed within the circuit and its subtree—so the circuit energy balance can be written as an 'inflows − outflows = consumption' equation.
energyConsumption = energyImported + energyProduced + energyRetrieved - energyReturned - energyStored
Where:
energyImported,energyReturnedare:meter readings for metered circuits, or
assumed values for unmetered circuits (as described above).
energyProduced,energyRetrieved,energyStoredare the subtree totals computed in Step 2.
Step 4: Residual consumption for a metered circuit (energyUsedThisLevel)
Residual consumption means: consumption that happens "at this circuit level", that is not separately metered in any part below it.
For a metered circuit:
energyUsedThisLevel = energyUsedTotal - energyUsedChildren

Explanation (diagram):
energyUsedTotalcovers the full subtree.If child circuits exist, their
energyUsedTotalrepresents consumption that can be attributed to those child branches.What remains is the residual consumption for this circuit level (
energyUsedThisLevel).
By definition, if a metered circuit has no child circuits:
energyUsedThisLevel == energyUsedTotal
For an unmetered circuit, energyUsedThisLevel is typically not meaningful in the same way, because it has no own meter-based balance. In this model, residual consumption is primarily a feature of metered circuits.